| Types of Trimming | Growth Rate | Distribution Voltage | ||
|---|---|---|---|---|
| 0 to 4 kV | 4 kV to 22 kV | 22 kV to 33 kV | ||
| Topping Clearance | Fast Growers | 6 ft. | 8 ft. | 9 ft. |
| Slow Growers | 4 ft. | 6 ft. | 7 ft. | |
| Side Clearance | Fast Growers | 4 ft. | 6 ft. | 8 ft. |
| Slow Growers | 2 ft. | 4 ft. | 6 ft. | |
| Overhead Clearance | Fast Growers | 4 ft. | 8 ft. | 12 ft. |
| Slow Growers | 2 ft. | 6 ft. | 12 ft. | |